Hydraulics
Hydraulics are an important part of any aquatic venue functionality. Aquatic venues must meet prescribed Maximum Allowable Turnover Times defined in the 2018 Aquatic Facility Regulations, Section 2-502.9:
“TURNOVER” means the period of time, usually expressed in hours, required to circulate a volume of water equal to the capacity of the AQUATIC VENUE. Pool Type and Turnover Cycle
Type of Aquatic Venue | Turnover Maximum |
---|---|
Activity Pools | 4 hours |
Diving Pools | 6 hours |
Interactive Water Play Venues* | 0.5 hours |
Isolation/Floatation Units* | 4 Turnovers between users |
Lazy Rivers | 4 hours |
Runout Slides | 4 hours |
Wading Pools* | 0.5 hours |
Child Amusement Lagoons* | 0.5 hours |
Wave Pools | 4 hours |
All Other Pools | 6 hours |
All Spas | 0.5 hours |
Surf Pools | Submit Engineering Justification from Equipment Manufacturer |
*Shall have secondary disinfection systems |
Documents to Submit
All forms below must be filled out and submitted by the appropriate person (engineer, architect, etc.)
- Calculation of Total Dynamic Head PDF
- Final Calculations PDF
- Face Piping PDF
- Individual Skimmer Piping PDF
- Inlet Piping PDF
- Main Drain Piping PDF
- Main Return Piping PDF
- Main Skimmer Piping PDF
- Minimum Design Flow Worksheet PDF
Additional forms to be completed only when appropriate for system:
- Heater Piping PDF
- Hydro Jet or Booster Line Return Piping PDF
- Booster Drain Piping PDF
- Booster Pump / System Final Calculations PDF
- Booster System Minimum / Design Flow Worksheet PDF